Starting system for fire water pump

Backup hydraulic starting system for Cummins QSK60DM driven Emergency Diesel Generator (EDG).
 

TECHNICAL INFORMATION
Requirements:3 consecutive starts 
Start duration:max 8 seconds each attempt
Recharge time :within 15-20 minutes
Engine:Cummins QSK60DM
Engine firing speed:150 rpm
Design code / Certification   :Designed acc. to ASME-U stamp 
for accumulators