Hatraco was awarded the contract for 3x Hydraulic start systems which are going to be used as the secondary startsystem for a fire water pump application. As per NFPA-20 requirements for a secondary start system, the start system provides the minimum of 6 times of 15 seconds of start duration.
The Clarke (JD) driven Fire water pumps are going to be deployed at a Techint project in South America. Sensed by a pressure pressure transmitter and a control panel for stand alone operation, the start system is automatically recharged by means of a electric motor recharge pump. All of Hatraco's hydraulic startsystems are equipped with a manual operated hydraulic pump as well. This enables our clients even to re-charge the system in a black out situation.
TECHNICAL INFORMATION
Project | : | Techint-Petrobras |
End user | : | Petrobras |
Location | : | South America |
EPCC | : | Techint group |
Start capacity | : | 6 x 38 Litres |
Start requirements | : | 6 times, 15 seconds each |
Recharge time | : | within 30 minutes |
Engine | : | JD 4045 |
Required engine firing speed | : | 110 - 120 RPM |
Application | : | JD 4045 (Clarke) diesel engine driven fire water pump |
Design code / Certification | : | Accumulator design according to ASME VIII Div 1, U stamped |
Specialties | : | Control panel for stand alone operation |
2 start valve manifolds for individual accumulator depletion |