Secondary start system for FWP

Hatraco was awarded the contract for 3x Hydraulic start systems which are going to be used as the secondary startsystem for a fire water pump application. As per NFPA-20 requirements for a secondary start system, the start system provides the minimum of 6 times of 15 seconds of start duration. 

The Clarke (JD) driven Fire water pumps are going to be deployed at a Techint project in South America. Sensed by a pressure pressure transmitter and a control panel for stand alone operation, the start system is automatically recharged by means of a electric motor recharge pump. All of Hatraco's hydraulic startsystems are equipped with a manual operated hydraulic pump as well. This enables our clients even to re-charge the system in a black out situation.


 

TECHNICAL INFORMATION
Project:Techint-Petrobras
End user:Petrobras
Location:South America
EPCC:Techint group
Start capacity:6 x 38 Litres
Start requirements :6 times, 15 seconds each
Recharge time:within 30 minutes
Engine:JD 4045
Required engine firing speed  :110 - 120 RPM
Application:JD 4045 (Clarke) diesel engine driven fire water pump
Design code / Certification   :Accumulator design according to ASME VIII Div 1, U stamped
Specialties:Control panel for stand alone operation
  2 start valve manifolds for individual accumulator depletion